Product overview: Fluke T6-600 Electrical Tester

Measure voltage … without test leads

Working in cramped electrical boxes and trying to find a safe metallic contact points is often challenging. The Fluke T6-600 Electrical Tester with FieldSense™ technology, lets you quickly and safely take measurements by sliding the open fork over a conductor, without the need for test leads. The T6-600 works with wires up to AWG 4/0 (120 mm2) with a 17.8 mm jaw opening

Key Features

Measure AC voltage and current without touching a live wire

Troubleshoot with all power supply measurements at-a-glance

See AC voltage and current values without test leads

Specifications: Fluke T6-600 Electrical Tester

Measurement Specifications

Function

Requires test leads

Range

Resolution

Accuracy[1]

FieldSense
ac voltage true-rms

No

600 V

1 V

±(3% + 3 counts) 45 Hz - 66 Hz[2] [3]

FieldSense
ac current true-rms

No

200.0 A

0.1 A

±(3% + 3 counts) 45 Hz - 66 Hz

Volts ac true-rms

Yes

600 V

1 V

±(1.5% + 2 counts) 45 Hz - 66 Hz

Volts dc

Yes

600 V

1 V

±(1% + 2 counts)

Resistance

Yes

2000 Ω

1 Ω

±(1% + 2 counts)

Safety

 

600 V CAT III

Accuracy[1]: ± ( [ % of reading] + [number of least significant digits] ). Accuracy is specified for 1 year after calibration, at 18 °C to 28 °C (64 °F to 82 °F) with relative humidity to 90 %. AC measurements are ac-coupled, RMS responding.

Accuracy[2]: Add 3 % without an external ground connection. External ground connection required for user wearing insulated gloves, standing on an insulated ladder, or otherwise insulated from earth ground.

Accuracy[3]: FieldSense is specified from 16 V to 100 % of range.

 

General Specifications

Calibration

1-year calibration cycle

Dimensions

61.1 x 259.3 x 43.8 mm

Jaw opening

17.8 mm

Weight

0.35 kg (0.78 lb)

Temperature

Operating

-10 °C to +50 °C (14 °F to 122 °F)

Storage

-30 °C to +60 °C (-22 °F to +140 °F)

Altitude

Operating

2,000 m (6,562 feet)

Storage

10,000 m (32,808 feet)

Relative Humidity

0% to 90%, 5 °C to 30 °C (41 °F to 86 °F)

0% to 75%, 30°C to 40 °C (86 °F to 104 °F)

0% to 45%, 40°C to 50 °C (104 °F to 122 °F)

Battery Type and Life

2 x AA (IEC LR6); 360 hours continuous, typical; 200 hours using FieldSense

Temperature coefficient

0.1 x (specified accuracy) / °C for <18°C or >28 °C

(< 64.4 °F or > 82.4 °F)

Safety

IEC/EN 61010-1: Pollution Degree 2

Electromagnetic Environment

IEC/EN 61326-1: Portable